Skip to product information
1 of 4

Applied Systems Technologies

5200 Flowmeter

5200 Flowmeter

Regular price $555.00 USD
Regular price Sale price $555.00 USD
Sale Sold out
Nom. Pipe Size

Overview

The CDI 5200 clamps onto a pipe, with two flow-sensing probes projecting into the pipe through 3/16-in. drilled holes. It seals directly to the pipe; no cutting or welding is required for installation. Because each flowmeter is made and calibrated for a specific size of pipe, the digital display indicates flow directly, with no setup or adjustment. $625 – $685.

Features

  • Easy to install
  • No moving parts
  • Weather resistant and surge protected
  • Milliamp output
  • Pulse output convertible to threshold output
  • User-configurable scaling, filtering and units of measure
  • Optional wired  outputs for networking

​The CDI 5200 is a true thermal-mass flowmeter, adapted for easy installation in existing piping systems. Its large, bright LED display is easy to read from a distance and its weather-proof enclosure and surge protection make it suitable for outdoor installation. A 4-20 mA output and a pulse output are standard; wired outputs are available as an option.

The CDI 5200 meters are commonly used for point-of-use monitoring of compressed air in textile mills, food packaging plants, groundwater remediation, printing plants and bottling plants; they are also widely used for branch-line monitoring.

The display can be configured to show flow in scfm, m3/min and m3/hr; it can also be configured to display daily usage or cumulative usage rather than current flow.

Technical Specs

Number of Rings

2 Rings

Type of Pipe

Metric Aluminum, Sch. 40 Steel, Type L Copper

Nominal Pipe Sizes

1/2 in. – 1-1/2 in., 25 mm – 40 mm, DN15 – DN40

Accuracy

5 percent of reading plus 1 percent of range for flows from 10 percent to 100 percent of indicated range at air temperatures between 20 and 120 degrees Fahrenheit

Fluids

Compressed Air, Nitrogen

Operating Pressure

200 psig maximum on Sch. 40 steel and on Type  L Copper; consult CDI for other materials and higher pressures.

Input Power

250 mA at 24 Vdc

Output Resistance

600 Ohms max.

Exposed Materials

Stainless steel, gold, thermal epoxy and Viton (seal)

Ring Material

Aluminum

Display

Four digit LED display

Response Time

One second to 63 percent of change in value at flows above 30 percent of range.

Resources

Click the files below to download

CDI 5000 Series Quickstart Guide

CDI 5200 Datasheet

CDI 5200 Instructions

CDI Flowmeter Ranges

CDI 5000 Series Wiring

CDI Rev. 3 Customization

Pressure-Sensing Option

CDI 5200 Shop Drawing

View full details